List of parameters
Parameter
1-335
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Re bit 03:
The hysteresis is set in p2150.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
Description: Displays the second status word for monitoring functions.
Note: Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
Description: Displays the third status word for monitoring functions.
Note: Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit will never be reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8010
05 n_set > 0 Yes No 8010
06 Motor stalled Yes No 8012
10 |M_set| < torque threshold value 1 Yes No 8012
11 Load monitoring signals an alarm Yes No 8013
12 Load monitoring signals a fault condition Yes No 8013
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2537
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010
04 Speed setp - act val deviation in tolerance
t_on
Yes No 8010
05 Ramp-up/ramp-down completed Yes No 8010
06 Current below the zero current threshold Yes No -
11 Torque utilization < torque threshold value 2 Yes No 8012