EasyManua.ls Logo

Siemens SINAMICS S110 - r2198.4...12 CO;BO: Status word monitoring 2; ZSW monitor 2; r2199.0...11 CO;BO: Status word monitoring 3; ZSW monitor 3

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameter
1-335
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Re bit 03:
The hysteresis is set in p2150.
Re bit 06:
The hysteresis is set in p2162.
Re bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
Description: Displays the second status word for monitoring functions.
Note: Re bit 10:
The torque threshold value 1 is set in p2174.
Re bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
Description: Displays the third status word for monitoring functions.
Note: Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit will never be reset.
Re bit 11:
The torque threshold value 2 is set in p2194.
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8010
05 n_set > 0 Yes No 8010
06 Motor stalled Yes No 8012
10 |M_set| < torque threshold value 1 Yes No 8012
11 Load monitoring signals an alarm Yes No 8013
12 Load monitoring signals a fault condition Yes No 8013
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2537
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010
04 Speed setp - act val deviation in tolerance
t_on
Yes No 8010
05 Ramp-up/ramp-down completed Yes No 8010
06 Current below the zero current threshold Yes No -
11 Torque utilization < torque threshold value 2 Yes No 8012