Parameter
List of parameters
1-350
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
2: Square function (x * x)
3: Cube function (x * x * x)
Dependency: Refer to: p2264, p2265, p2267, p2268, p2269, p2271
Description: Setting to invert the actual value signal of the technology controller.
The inversion depends on the sensor type for the actual value signal.
Value: 0: No inversion
1: Inversion actual value signal
Caution: If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note: The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal of the technology controller.
--> If the actual value increases as the motor speed increases, then p2271 should be set to 0 (no inversion).
--> If the actual value decreases as the motor speed increases, then p2271 should be set to 1 (the actual value sig-
nal is inverted).
Description: Displays the scaled actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, r2266, p2267, p2268, p2269, p2270, p2271
Description: Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency: Refer to: p2263
p2271 Technology controller actual value inversion (sensor type) / Tech_ctrl act inv
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r2272 CO: Technology controller actual value scaled / Tech_ctrl act scal
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r2273 CO: Technology controller error / Tec_ctrl error
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]