Siemens SINAMICS S110 - p0429[0...n] Encoder SSI configuration; Enc SSI config; p0430[0...n] Sensor Module configuration; SM config

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-102
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Description: Sets the configuration for an SSI encoder.
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400). When selecting a catalog
encoder, this parameter cannot be changed (write protection). Information in p0400 should be carefully observed
when removing write protection.
Note: Re bit 06:
The quiescent signal level of the data line corresponds to the inverted, set level.
Description: Sets the configuration of the Sensor Module.
Notice: A bit-wise configuration is only possible if the corresponding property is also present in r0458.
Note: Re bit 17 (burst oversampling):
- if bit = 1, burst oversampling is switched on.
Re bit 18 (continuous oversampling):
- if bit = 1, continuous oversampling is switched on.
Re bit 19 (Safety position actual value sensing):
- if bit = 1, the Safety position actual value is transferred in the cyclic telegram.
p0429[0...n] Encoder SSI configuration / Enc SSI config
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Transfer code Binary code Gray code -
02 Transfer absolute value twice Yes No -
06 Data line during the monoflop time High level Low level -
p0430[0...n] Sensor Module configuration / SM config
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1110 0000 0000 1000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
17 Burst oversampling Yes No -
18 Continuous oversampling (reserved) Yes No -
19 Safety position actual value sensing Yes No -
20 Speed calculation mode (only SMC30) Incremental diff Flank time meas -
21 Zero mark tolerance Yes No -
22 Rot pos adapt Yes No -
23 De-select commutation with zero mark Yes No -
24 Commutation with selected zero mark Yes No -
25 Switch off encoder voltage supply during
parking
Yes No -
27 Extrapolate position values Yes No -
28 Cubic correction Yes No -
29 Phase correction Yes No -
30 Amplitude correction Yes No -
31 Offset correction Yes No -