List of parameters
Parameter
1-105
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the position and level of the alarm bit in the SSI protocol.
Notice: The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note: Value = dcba
ba: Position of the alarm bit in protocol (0 ... 63).
c: Level (0: Low level, 1: High level).
d: State of the evaluation (0: Off, 1: On).
Example:
p0435 = 1014
--> The evaluation is switched in and the alarm bit is at position 14 with a low level.
p0435 = 1114
--> The evaluation is switched in and the alarm bit is at position 14 with a high level.
Description: Sets the position and parity of the parity bit in the SSI protocol.
Notice: The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note: Value = dcba
ba: Position of the parity bit in the protocol (0 ... 63).
c: Parity (0: even, 1: uneven).
d: State of the evaluation (0: Off, 1: On).
Example:
p0436 = 1015
--> The evaluation is switched in and the parity bit is at position 15 with even parity.
p0436 = 1115
--> The evaluation is switched in and the parity bit is at position 15 with uneven parity.
Description: Sets the extended configuration of the Sensor Module.
p0435[0...n] Encoder SSI alarm bit / Enc SSI alarm bit
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p0436[0...n] Encoder SSI parity bit / Enc SSI parity bit
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p0437[0...n] Sensor Module configuration extended / SM config ext
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: EDS, p0140 Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0011 0000 0000 0000 0000
1000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Data logger Yes No -
01 Zero mark edge detection Yes No -
02 Correction position actual value XIST1 Yes No -
04 Edge evaluation bit 0 Yes No -