EasyManua.ls Logo

Siemens SINAMICS S110 - r4709[0...1] Trace memory space required for measuring functions; Trace mem required; p4710[0...1] Trace trigger condition; Trace Trig_cond; p4711[0...5] Trace trigger signal; Trace trig_signal

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-452
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the memory space required for the current parameter setting in bytes, if the trace is used for the measur-
ing functions.
Index: [0] = Trace 0
[1] = Trace 1
Dependency: Refer to: r4799
Description: Sets the trigger condition for the trace.
Value: 1: Immediate start
2: Positive edge
3: Negative edge
4: Entry to hysteresis band
5: Leaving hysteresis band
6: Trigger at bit mask
7: Start with function generator
Index: [0] = Trace 0
[1] = Trace 1
Description: Selects the trigger signal for the trace.
Index: [0] = Trace 0 parameter in BICO format
[1] = Trace 1 parameter in BICO format
[2] = Trace 0 PINx with DO Id and chart Id
[3] = Trace 0 PINx with block Id and PIN Id
[4] = Trace 1 PINy with DO Id and chart Id
[5] = Trace 1 PINy with block Id and PIN Id
Dependency: Only effective when p4710 does not equal 1.
Note: It only makes sense to trace the PINs using the commissioning software.
For index 2(4) and 3(5) equal to zero, index 0(1) can only be written and vice versa.
Re index 0 ... 1:
Here, the trigger signal for trace 0 or 1 is entered as parameter in the BICO format.
For trace with a physical address (p4789), the data type of the trigger signal is set here.
r4709[0...1] Trace memory space required for measuring functions / Trace mem required
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -
p4710[0...1] Trace trigger condition / Trace Trig_cond
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
1 7 2
p4711[0...5] Trace trigger signal / Trace trig_signal
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - 0

Table of Contents

Other manuals for Siemens SINAMICS S110

Related product manuals