List of parameters
Parameter
1-719
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the signal source of input quantity X and of setting value SV of instance PT1 0 of the smoothing element.
Index: [0] = Input X
[1] = Setting value SV
Description: Sets the signal source for the "accept setting value" signal of instant PT1 0 of the smoothing element.
Description: Sets the smoothing time constant T in milliseconds of instance PT1 0 of the smoothing element.
Description: Display parameter for the smoothed output quantity Y of instance PT1 0 of the smoothing element.
p20244[0...1] CI: PT1 0 inputs / PT1 0 inputs
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN,
SERVO_S110-CAN
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / FloatingPoint32 Dynamic index: - Func. diagram: 7262
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p20245 BI: PT1 0 accept setting value S / PT1 0 acc set val
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN,
SERVO_S110-CAN
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 7262
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p20246 PT1 0 smoothing time constant in ms / PT1 0 T_smooth ms
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN,
SERVO_S110-CAN
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Can be changed: T Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7262
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 340.28235E36 0.00
r20247 CO: PT1 0 output Y / PT1 0 output Y
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN,
SERVO_S110-CAN
(FBLOCKS),
SERVO_S110-DP
(FBLOCKS),
SERVO_S110-PN
(FBLOCKS)
Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7262
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - -

Table of Contents