List of parameters
Parameter
1-235
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: Refer to: p1317, p1338, p1349
Note: The filter time constant must be greater than the oscillation period of the oscillation to be dampened.
Description: Sets the proportional gain for DC braking (p1230, p1231).
Dependency: Refer to: p1346
Note: Current controller adaptation is not effective for DC braking.
Description: Sets the integral time for DC braking (p1230, p1231).
Dependency: Refer to: p1345
Note: For p1346 = 0, the following applies:
The integral time of DC braking is de-activated.
Description: Sets the maximum output frequency for resonance damping for U/f control.
Resonance damping is inactive above this output frequency.
Dependency: Refer to: p1338, p1339
Note: Resonance damping is active in the following ranges:
- Active: 3.1 Hz ... p1349
- Build-up (linear): 3.1 ... 4.77 Hz
- Reduction (linear): 0.95 * p1349 ... p1349
Description: Sets the configuration for the closed-loop speed control.
p1345[0...n] DC braking proportional gain / DCBRK Kp
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 100000.000 0.000
p1346[0...n] DC braking, integral time / DCBRK Tn
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [ms] 50.000 [ms] 0.030 [ms]
p1349[0...n] U/f mode resonance damping maximum frequency / Uf res_damp f_max
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 3000.00 [Hz]
p1400[0...n] Speed control configuration / n_ctrl config
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: DDS, p0180 Func. diagram: 1590, 5490
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0011 1010 0000 bin