List of parameters
Parameter
1-313
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Setting to invert the individual binector outputs of the connector-binector converter.
Using p2098[0], the signals of CI: p2099[0] are influenced.
Using p2098[1], the signals of CI: p2099[1] are influenced.
Dependency: Refer to: r2094, r2095, p2099
Description: Sets the signal source for the connector-binector converter.
A PZD receive word can be selected as signal source. The signals are available to be serially passed-on (intercon-
nection).
Dependency: Refer to: r2094, r2095
Note: From the signal source set via the connector input, the corresponding lower 16 bits are converted.
p2099[0...1] together with r2094.0...15 and r2095.0...15 forms two connector-binector converters:
Connector input p2099[0] to binector output in r2094.0...15
Connector input p2099[1] to binector output in r2095.0...15
Description: Selects the faults for which the fault response should be changed
p2098[0...1] Inverter connector-binector converter binector output / Con/bin outp inv
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2468
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 Inverted Not inverted -
01 Bit 1 Inverted Not inverted -
02 Bit 2 Inverted Not inverted -
03 Bit 3 Inverted Not inverted -
04 Bit 4 Inverted Not inverted -
05 Bit 5 Inverted Not inverted -
06 Bit 6 Inverted Not inverted -
07 Bit 7 Inverted Not inverted -
08 Bit 8 Inverted Not inverted -
09 Bit 9 Inverted Not inverted -
10 Bit 10 Inverted Not inverted -
11 Bit 11 Inverted Not inverted -
12 Bit 12 Inverted Not inverted -
13 Bit 13 Inverted Not inverted -
14 Bit 14 Inverted Not inverted -
15 Bit 15 Inverted Not inverted -
p2099[0...1] CI: Connector-binector converter signal source / Con/bin S_src
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dynamic index: - Func. diagram: 2468
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2100[0...19] Setting the fault number for fault response / F_no F response
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 1750, 8075
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0