List of parameters
Parameter
1-177
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
111: SIEMENS telegram 111, PZD-12/12
999: Free telegram configuration with BICO
Dependency: Refer to: p2038
Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
Value: 999: Free telegram configuration with BICO
Dependency: Refer to: p2038
Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Displays the position of the "Pulses enabled" status signal in the PROFIdrive telegram.
Index: [0] = Signal number
[1] = Bit position
Description: Sets the number of tolerated consecutive sign-of-life errors of the clock-cycle synchronous master.
The sign-of-life signal is normally received in PZD4 (control word 2) from the master.
Dependency: Refer to: p2045, r2065
Refer to: F01912
Note: The sign-of-life monitoring is disabled for p0925 = 65535.
p0922 IF1 PROFIdrive telegram selection / IF1 PD Telegr_sel
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2424
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
999 999 999
r0924[0...1] ZSW bit pulses enabled / ZSW pulse enab
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2454, 2456
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p0925 PROFIdrive clock synchronous sign-of-life tolerance / PD SoL_tol
CU_S110-DP,
CU_S110-PN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 1