List of parameters
Parameter
1-91
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Induction motor, separately-excited synchronous motor: Sets the rotor leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910).
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The reference value for p0326 is inversely proportional to the leakage inductance of the motor (p0353, p0354,
p0356).
Description: Sets the rotor/secondary section leakage inductance of the motor.
For separately-excited synchronous motors: Sets the damping inductance in the rotor direction (d-axis).
This value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identification routine
(p1910) (not for separately-excited synchronous motors).
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
VECTOR:
If the rotor leakage inductance (p0358) for induction motors is changed outside the commissioning phase (p0010 >
0), then the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then
advised to repeat the measurement for the saturation characteristic (p1960).
Description: Sets the magnetizing inductance of the motor.
For separately-excited synchronous motors: Sets the saturated magnetizing inductance in the rotor direction (d-
axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor identifica-
tion routine (p1910) (not for separately-excited synchronous motors).
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
p0356[0...n] Motor stator leakage inductance / Mot L_stator leak.
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0358[0...n] Motor rotor leakage inductance / damping inductance, d axis / Mot L_r leak / LDd
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0360[0...n] Motor magnetizing inductance/magn. inductance, d axis saturated / Mot Lh/Lh d sat
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 10000.00000 [mH] 0.00000 [mH]