List of parameters
Parameter
1-157
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: The simulation of a digital input is selected using p0795.
Refer to: p0795
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Sets the simulation mode for the analog input.
Value: 0: No simulation mode for analog input x
1: Simulation mode for analog input x
Dependency: The setpoint for the input voltage is specified via p0798.
Refer to: p0798
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description: Sets the setpoint for the input value in the simulation mode of the analog input.
Dependency: The simulation of an analog input is selected using p797.
If AI is parameterized as voltage input (p756), then the setpoint is a voltage in V.
If AI is parameterized as current input (p756), then the setpoint is current in mA.
Refer to: p0756, p0797
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description: Sets the sampling time for the inputs and outputs of the Control Unit.
18 DI 18 (X130.4) High Low -
19 DI 19 (X130.5) High Low -
20 DI 20 (X131.1) High Low -
21 DI 21 (X131.2) High Low -
22 DI 22 (X131.4) High Low -
p0797 CU analog input simulation mode / CU AI sim_mode
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0798 CU analog input simulation mode setpoint / CU AI sim setp
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 [V] 20.000 [V] 0.000 [V]
p0799[0...2] CU inputs/outputs, sampling time / CU I/O t_sampl
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: C1(3) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2020, 2030,
2031
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1000.00 [µs] 5000.00 [µs] 4000.00 [µs]