List of parameters
Parameter
1-163
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the signal source for the feedback signal of the contactors when changing over motors.
There is a fixed inter-relationship between energizing the contactor and the feedback signal.
Example:
A changeover is to be made between MDS0 (motor 0) and MDS1 (motor 1). The contactors should be switched
using bit 4 (contactor 0) and 5 (contactor 1). The changeover should be made with an interconnection of the feed-
back signal.
Implementation:
MDS0: p0827[0] = 4, interconnect output to switch contactor 0 to r0830.4, p0831[4] = "input, feedback signal, con-
tactor 0"
MDS1: p0827[1] = 5, interconnect output to switch contactor 1 to r0830.5, p0831[5] = "input, feedback signal, con-
tactor 1"
The following sequence applies when changing over from MDS0 to MDS1:
1. The status bit r0830.4 is deleted. When the feedback signal (p0831[4]) is connected, the system waits until the
feedback signal "contactor open" is displayed. If the feedback signal is not connected, then the system waits for the
switch-off interlocking time of 320 ms.
2. The status bit r0830.5 is set. If the feedback signal (p0831[5]) is connected, the system waits until the feedback
signal "contactor closed" is displayed. If the feedback signal is not connected, then the system waits for the switch-
on interlocking time of 160 ms.
Index: [0] = Feedback signal contactor 0
[1] = Feedback signal contactor 1
[2] = Feedback signal contactor 2
[3] = Feedback signal contactor 3
[4] = Feedback signal contactor 4
[5] = Feedback signal contactor 5
[6] = Feedback signal contactor 6
[7] = Feedback signal contactor 7
[8] = Feedback signal contactor 8
[9] = Feedback signal contactor 9
[10] = Feedback signal contactor 10
[11] = Feedback signal contactor 11
[12] = Feedback signal contactor 12
[13] = Feedback signal contactor 13
[14] = Feedback signal contactor 14
[15] = Feedback signal contactor 15
Description: Displays the status word of the contactor feedback signals when changing over a motor.
p0831[0...15] BI: Motor changeover, contactor feedback / Mot_chg cont fdbk
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 8575
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r0832.0...15 CO/BO: Mot. changeover, contactor feedback sig. status word / Mot_chng fdbk ZSW
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Feedback signal contactor 0 Closed Opened -
01 Feedback signal contactor 1 Closed Opened -
02 Feedback signal contactor 2 Closed Opened -
03 Feedback signal contactor 3 Closed Opened -
04 Feedback signal contactor 4 Closed Opened -