List of parameters
Parameter
1-145
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: Refer to: r0723
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Displays the inverted status of the digital inputs.
Dependency: Refer to: r0722
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
Description: Sets the bidirectional digital inputs/outputs as an input or output.
Note: DI/DO: Bidirectional Digital Input/Output
21 DI 21 (X131.2) High Low -
22 DI 22 (X131.4) High Low -
r0723.0...22 CO/BO: CU digital inputs, status inverted / CU DI status inv
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 1510, 2020,
2030, 2031, 2100, 2120, 2130,
2131, 2132, 2133
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X133.1) High Low -
01 DI 1 (X133.2) High Low -
02 DI 2 (X133.3) High Low -
03 DI 3 (X133.4) High Low -
08 DI/DO 8 (X132.1) High Low -
09 DI/DO 9 (X132.2) High Low -
10 DI/DO 10 (X132.3) High Low -
11 DI/DO 11 (X132.4) High Low -
16 DI 16 (X130.1) High Low -
17 DI 17 (X130.2) High Low -
18 DI 18 (X130.4) High Low -
19 DI 19 (X130.5) High Low -
20 DI 20 (X131.1) High Low -
21 DI 21 (X131.2) High Low -
22 DI 22 (X131.4) High Low -
p0728 CU, set input or output / CU DI or DO
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 1510, 2030,
2031
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X132.1) Output Input 2030
09 DI/DO 9 (X132.2) Output Input 2030
10 DI/DO 10 (X132.3) Output Input 2031
11 DI/DO 11 (X132.4) Output Input 2031