Siemens SINAMICS S110 - r0774[0...2] Test sockets output voltage; TestSkts U_output; p0776[0...2] Test socket mode; Test skt mode; p0777[0...2] Test socket characteristic value x1; Test skt char x1

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-152
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Refer to: p0771, r0774, p0776, p0777, p0778, p0779, p0780, p0783, p0784, r0786
Description: Displays the actual output voltage for the test sockets.
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Refer to: p0771, r0772, p0776, p0777, p0778, p0779, p0780, p0783, p0784, r0786
Description: Sets the mode for the test sockets.
Value: 96: Physical address (32-bit integer signal unsigned)
97: Physical address (32-bit integer signal)
98: Physical address (32-bit floating-point signal)
99: BICO signal
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784, r0786, p0788, p0789, r0790
Description: The scaling characteristic for the test sockets is defined using two points. This parameter specifies the x coordinate
(percentage) of the first point on the characteristic.
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Can only be set when p0776 = 99.
Refer to: p0778, p0779, p0780, r0786
Note: The value 0.00 % corresponds to 2.49 V.
r0774[0...2] Test sockets output voltage / TestSkts U_output
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p0776[0...2] Test socket mode / Test skt mode
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
96 99 99
p0777[0...2] Test socket characteristic value x1 / Test skt char x1
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-100000.00 [%] 100000.00 [%] 0.00 [%]