Parameter
List of parameters
1-48
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the measured actual phase currents as peak value.
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
[3] = Phase U offset
[4] = Phase V offset
[5] = Phase W offset
[6] = Total U, V, W
Note: In indices 3 ... 5, the offset currents of the 3 phases, which are added to correct the phase currents, are displayed.
The sum of the 3 corrected phase currents is displayed in index 6.
Description: Displays the measured actual value of the DC link voltage.
Dependency: Refer to: r0026
Notice: For SINAMICS S120 AC Drive (AC/AC) the following applies:
When measuring a DC link voltage < 200 V, for the Power Module (e.g. PM340) a valid measured value is not sup-
plied. In this case, when an external 24V power supply is connected, a value of approx. 24 V is displayed.
Note: The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
Description: Displays the actual power unit output voltage (Motor Module).
Dependency: Refer to: r0025
Note: The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0069[0...6] Phase current actual value / I_phase act value
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 1630, 5730,
6714, 6730, 6731, 8850, 8950
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r0070 CO: Actual DC link voltage / Vdc act val
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 5730
P-Group: Displays, signals Units group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r0072 CO: Output voltage / U_output
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 1630, 5730,
6730, 6731, 6799
P-Group: Displays, signals Units group: 5_1 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]