List of parameters
Parameter
1-543
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SS1: Safe Stop 1
Description: Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP
A).
Dependency: Refer to: p9356, p9560
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SS1: Safe Stop 1
Description: Sets the stop response for the function "Safely-Limited Speed" (SLS).
These settings apply to the individual limit values for SLS.
In the case of encoderless motion monitoring (p9306 = 1), only a value of 0 or 1 is permitted.
Value: 0: STOP A
1: STOP B
2: STOP C
3: STOP D
4: STOP E
10: STOP A with delayed pulse suppression when the bus fails
11: STOP B with delayed pulse suppression when the bus fails
12: STOP C with delayed pulse suppression when the bus fails
13: STOP D with delayed pulse suppression when the bus fails
14: STOP E with delayed pulse suppression when the bus fails
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency: Refer to: p9331, p9380, p9563
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The values 4 and 14 are not supported on Control Unit 305.
SLS: Safely-Limited Speed
p9360 SI Motion pulse suppression shutdown speed (Motor Module) / SI Mtn IL n_sh MM
SERVO_S110-CAN
(Safety rot),
SERVO_S110-DP
(Safety rot),
SERVO_S110-PN
(Safety rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 6000.00 [rpm] 0.00 [rpm]
p9363[0...3] SI Motion SLS stop response (processor 2) / SI Mtn SLS stop P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 14 2