List of parameters
Parameter
1-297
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: Refer to: p2051, p2061
Note: IF1: Interface 1
Description: Status display for the PROFIBUS interface.
Value: 0: OFF
1: No connection (search for baud rate)
2: Connection OK (baud rate found)
3: Cyclic connection with master (data exchange)
4: Cyclic data OK
Note: Re r2054 = 3:
In state 3 (the LED flashes green), a cyclic connection has been established to the PROFIBUS master; however,
one of the following prerequisites is missing for cyclic operation:
- No setpoints are being received as the PROFIBUS master is in the STOP condition.
Only for clock-cycle synchronous operation, the following applies:
- The drive is not in synchronism as the global control (GC) has an error.
Re r2054 = 4:
In the status 4 (LED green), the cyclic connection to the PROFIBUS master has been established and setpoints are
being received. The clock cycle synchronization is OK, the global control (GC) is error-free.
This state does not provide any statement regarding the quality of the clock cycle synchronous sign-of-life charac-
ters on the drive objects.
Description: Diagnostics display for the PROFIBUS interface.
Index: [0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
Description: Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency: Refer to: p0918
r2054 PROFIBUS status / PB status
CU_S110-DP Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 -
r2055[0...2] PROFIBUS diagnostics standard / PB diag standard
CU_S110-DP Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r2057 PROFIBUS address switch diagnostics / PB addr diagn
CU_S110-DP Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -