Overview of faults and alarms
Faults and alarms
3-969
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Acknowledging faults
The list of faults and alarms specifies how to acknowledge each fault after the
cause has been remedied.
Table 3-3 Acknowledging faults
Acknowledg-
ment
Description
POWER ON The fault is acknowledged by a POWER ON (switch drive unit off and on again).
Note:
If this action has not eliminated the fault cause, the fault is displayed again immediately
after power up.
IMMEDIATELY Faults can be acknowledged on one drive object (Points 1 to 3) or on all drive objects
(Point 4) as follows:
1 Acknowledging by setting parameter:
p3981 = 0 --> 1
2 Acknowledging via binector inputs:
p2103
p2104
p2105
BI: 1. Acknowledge faults
BI: 2. Acknowledge faults
BI: 3. Acknowledge faults
3 Acknowledging via a PROFIBUS control signal:
STW1.7 = 0 --> 1 (edge)
4 Acknowledge all faults
p2102 BI: Acknowledge all faults
All of the faults on all of the drive objects of the drive system can be acknowledged
using this binector input.
Note:
These faults can also be acknowledged by a POWER ON operation.
If this action has not eliminated the fault cause, the fault will continue to be displayed
after acknowledgment.
Safety Integrated faults
The "Safe standstill" (SH) function must be deselected before these faults are
acknowledged.
PULSE INHIBIT The fault can only be acknowledged with a pulse inhibit (r0899.11 = 0).
The same options are available for acknowledging as described under acknowledgment
with IMMEDIATELY.