SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
101
2 Parameters
2.2 List of parameters
Description: Sets the number of Command Data Sets (CDS).
Note: It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
Description: Sets the number of Command Data Sets (CDS).
Note: It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
Description: The function module of an existing drive object is entered into each index (see p0101, p0107).
The following bits are available in p0171 for the Control Unit (Index 0):
- still none
For all other drive objects (Index > 0), the significance of the bits should be taken from the display parameters r0171
of the drive object.
p0170 Number of Command Data Sets (CDS) / CDS count
VECTOR_G Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2 4 2
p0170 Number of Command Data Sets (CDS) / CDS count
B_INF Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 2 1
p0171[0...n] Drive objects function module 1 / DO fct_mod 1
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: C1(2) Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bit 0 ON OFF -
01 Bit 1 ON OFF -
02 Bit 2 ON OFF -
03 Bit 3 ON OFF -
04 Bit 4 ON OFF -
05 Bit 5 ON OFF -
06 Bit 6 ON OFF -
07 Bit 7 ON OFF -
08 Bit 8 ON OFF -
09 Bit 9 ON OFF -
10 Bit 10 ON OFF -
11 Bit 11 ON OFF -
12 Bit 12 ON OFF -
13 Bit 13 ON OFF -
14 Bit 14 ON OFF -
15 Bit 15 ON OFF -
16 Bit 16 ON OFF -
17 Bit 17 ON OFF -
18 Bit 18 ON OFF -
19 Bit 19 ON OFF -
20 Bit 20 ON OFF -
21 Bit 21 ON OFF -