SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
203
2 Parameters
2.2 List of parameters
Notice: Information on Gn_STW/Gn_ZSW can, e.g. be found in the following literature:
SINAMICS S120 Function Manual Drive Functions
Note: For bit 14:
Displays the acknowledgment for "activate parking encoder" (Gn_STW.14 = 1) or encoder position actual value
(Gn_XIST1) invalid.
For bit 14, 15:
r0481.14 = 1 and r0481.15 = 0 can have one of the following causes:
- the encoder is parked.
- the encoder is deactivated.
- the encoder is being commissioned.
- no parameterized encoder available.
- encoder data set is being changed over.
r0481.14 = 1 and r0481.15 = 1 has the following significance:
An encoder error has occurred and the encoder position actual value (Gn_XIST1) is invalid.
Description: Display and connector output for the encoder actual position value Gn_XIST1 according to PROFIdrive.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Note: - this value is reset if necessary when the "parking encoder" (r0481.14) function is de-selected.
- in this value, the measuring gear (p0432, p0433) is only taken into account when the position tracking is activated
(p0411.0 = 1).
- the update time for the position control (EPOS) corresponds to the position controller clock cycle p0115[4].
- the update time in isochronous operation corresponds to the bus cycle time r2064[1].
- the update time in isochronous operation and with position control (EPOS) corresponds to the position controller
clock cycle p0115[4].
- the update time in non-isochronous operation or without position control (EPOS) comprises the following:
Update time = 4 * least common multiple (LCM) of all current controller clock cycles (p0115[0]) in the drive group
(infeed + drives).
The minimum update time is 1 ms.
Example 1: infeed, servo
Update time = 4 * LCM(250 µs, 125 µs) = 4 * 250 µs = 1 ms
Example 2: infeed, servo, vector
Update time = 4 * LCM(250 µs, 125 µs, 500 µs) = 4 * 500 µs = 2 ms
04 Value 1 Displayed in r0483 Not present -
05 Value 2 Displayed in r0483 Not present -
06 Value 3 Displayed in r0483 Not present -
07 Value 4 Displayed in r0483 Not present -
08 Measuring probe 1 deflected Yes No -
09 Measuring probe 2 deflected Yes No -
11 Encoder fault acknowledge active Yes No 9676
13 Absolute value cyclically Displayed in r0483 No -
14 Parking encoder active Yes No -
15 Encoder fault Displayed in r0483 None -
r0482[0...2] CO: Encoder actual position value Gn_XIST1 / Enc Gn_XIST1
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 4700, 4702,
4704, 4735, 4740, 4750
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -