F30804 (N, A) Power unit: CRC
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: LOCAL
Reaction: Vector: OFF2 (OFF1, OFF3)
Infeed: OFF2 (OFF1)
Acknowledge: IMMEDIATELY
Cause: A checksum error (CRC error) has occurred for the power unit.
Remedy: - carry out a POWER ON (switch off/on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F30805 Power unit: EEPROM checksum error
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: LOCAL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy: Replace the module.
F30809 Power unit: Switching information not valid
Message value: -
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: LOCAL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: For 3P gating unit, the following applies:
The last switching status word in the setpoint telegram is identified by the end ID. Such an end ID was not found.
Remedy: - carry out a POWER ON (switch off/on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
A30810 (F) Power unit: Watchdog timer
Message value: -
Message class: Hardware/software error (1)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: When booting it was detected that the cause of the previous reset was an SAC watchdog timer overflow.
Remedy: - carry out a POWER ON (switch off/on) for all components.
- upgrade firmware to later version.
- contact Technical Support.