2 Parameters
2.2 List of parameters
SINAMICS G130/G150
606 List Manual (LH2), 07/2016, A5E03263479A
Note: The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description: Displays the internal status of the infeed module.
Value: 0: Initialization
1: Fault
2: No ON command
3: Offset measurement running
4: ON delay active
5: Precharging running
6: Operation
Description: Display and BICO output for the status word of the DC link voltage control.
Dependency: Refer to: A06810
Note: For bit 01:
DC link voltage control is disabled and enabled with p3513.
For bit 08 = 1:
DC link voltage control is selected using p3513.
Description: Display and BICO output for the status word of the infeed unit.
Dependency: Refer to: A06810
Note: For bit 07:
When the alarm threshold is fallen below, alarm A06810 is output and r3405.7 is set = 1.
The alarm threshold is obtained from the sum of the undervoltage threshold p0296 and offset r0279. As a
consequence, the alarm threshold is only effective for p0279 > 0.
Monitoring only takes place when operational.
The following applies for states r3402 <= 5 and r3402 = 12: r3405.7 = 0.
r3402 Infeed status internal BIC / INF state int
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8932
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 6 -
r3405.1...8 CO/BO: Status word DC link control / ZSW Vdc_ctrl
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 Vdc-ctrl active Yes No -
08 Vdc controller selected Yes No -
r3405.7 CO/BO: Infeed status word / Inf ZSW
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 DC link undervoltage alarm threshold
undershot
Yes No -