4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1524 List Manual (LH2), 07/2016, A5E03263479A
F05059 Parallel circuit: VSM firmware versions differ
Message value: Parameter: %1
Message class: General drive fault (19)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The firmware versions of the Voltage Sensing Module (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the first different version number was detected.
Remedy: For parallel circuit configurations, only Voltage Sensing Modules (VSM) with identical firmware versions may be
used.
F05060 Parallel circuit: Power unit firmware version does not match
Message value: Parameter: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: B_INF, VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: Firmware from version V02.30.01.00 is required when connecting the power units in parallel.
Remedy: Update the firmware of the power units (at least V02.30.01.00).
F05061 Infeed VSM count
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: B_INF, VECTOR_G
Component: Voltage Sensing Module (VSM) Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The number of active Voltage Sensing Modules (VSM) for the drive object infeed with chassis power units is not
correct.
For A_Infeed, each active power unit must be assigned an active VSM also for a parallel circuit configuration.
For S_Infeed, the active drive object, must be assigned at least one active VSM.
Fault value (r0949, interpret decimal):
Number of VSMs that are currently assigned to the drive object.
Remedy: Adapts the number of active Voltage Sensing Modules (VSM).
F05064 Parallel connection: Pulse synchronization error
Message value: -
Message class: General drive fault (19)
Drive object: VECTOR_G
Component: Power Module Propagation: GLOBAL
Reaction: OFF2 (OFF1, OFF3)
Acknowledge: POWER ON (IMMEDIATELY)
Cause: The pulse synchronization of at least one of the power units connected in parallel is incorrect.
Remedy: Restart the drive system.