2 Parameters
2.2 List of parameters
SINAMICS G130/G150
500 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the serial interface for the debug monitor.
The serial interface for the debug monitor is COM1 (X140) or COM2 (internal).
Value = 0: COM2 (internal)
Value = 1: COM1 (X140), commissioning protocol is deactivated
Value = 2: COM2 (internal)
Value = 3: Reserved
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency: Refer to: p2030
Note: The parameter is only relevant for the setting of the following fieldbus protocols.
- USS (X140) (p2030 = 6)
- Modbus TCP (p2030 = 13)
Value = 0: Monitoring is deactivated.
Description: Sets the PROFIBUS ident number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with ident number 3AA0 hex).
Value: 0: SINAMICS
1: VIK-NAMUR
Note: Every change only becomes effective after a POWER ON.
p2039 Select debug monitor interface / Debug monit select
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9310
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1999999 [ms] 100 [ms]
p2042 PROFIBUS Ident Number / PB ident No.
CU_G130_DP,
CU_G150_DP
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0