List Manual (LH2), 07/2016, A5E03263479A
777
2 Parameters
2.2 List of parameters
Description: Setting of the tolerance window for the sign of life monitoring for communication to the power unit.
Dependency: Refer to: A30853
Note: An active window is generated by means of DRIVE-CLiQ telegrams.
If more than one sign-of-life error appears in the window, then A30853 is output.
The lower the value in p7788, the greater the monitoring tolerance.
Description: Sets the number of consecutive sign-of-life errors that are tolerated for communication to the power unit.
Dependency: Refer to: F30008
Note: F30008 is output in the case of a fault.
The higher the value in the parameter, the higher the monitoring tolerance.
Description: Sets the individual signals for the component trace.
For p7790[0...15] = 0, the component trace is deactivated.
For index 0 ... 7:
The signals are set in p7790[0...7], whose characteristic is to be recorded over time.
If "No signal" is set for a trace channel, then the recording duration of the other time characteristics is increased.
For index 8 ... 15:
The signals are set in p7790[8...15], whose instantaneous value is to be recorded.
Value: 0: No signal
1: Pulse frequency
2: Phase current U
3: Phase current V
p7788 Power unit sign-of-life monitoring tolerance window / PU SoL monit tol
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 1000 10
p7789 Power unit sign-of-life monitoring fault threshold / PU SoL monit F_thr
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1000 1
p7790[0...15] Component trace signal / Comp trace sig
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 9 [0] 2
[1] 3
[2] 4
[3] 7
[4] 8
[5] 9
[6] 5
[7] 0
[8] 6
[9] 1
[10...15] 0