SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
219
2 Parameters
2.2 List of parameters
Description: Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: p0496, r0497, r0498
Description: Displays the trace signal for encoder diagnostics (high component).
The signal to be output is selected in p0496.
Dependency: Refer to: p0496, r0497, r0498
Description: Sets the technology application.
The parameter influences the calculation of open-loop and closed-loop control parameters that is e.g. initiated using
p0578.
Value: 0: Standard drive (VECTOR)
1: Pumps and fans
2: Sensorless closed-loop control down to f = 0 (passive loads)
4: Dynamic in the field weakening range
5: Starting with a high break loose torque
6: High LoadMomInert
Dependency: Refer to: p2175, p2177
Note: The calculation of parameters dependent on the technology application can be called up as follows:
- when exiting quick commissioning using p3900 > 0
- when writing p0340 = 1, 3, 5 (for p0500 = 6: p0340 = 1, 3, 4)
- when writing p0578 = 1
For p0500 = 0 and when the calculation is initiated, the following parameters are set:
- p1574 = 10 V (separately excited synchronous motor: 20 V)
- p1750.2 = 0
- p1802 = 4 (SVM/FLB without overcontrol)
- p1803 = 106 %
- p1610 = 50 %
- p1611 = 30 %
- p1310 = 50 %
r0499[0...2] CO: Encoder diagnostic signal high word / Enc diag high word
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r0499 Encoder diagnostic signal high word / Enc diag high word
ENC Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p0500 Technology application / Tec application
VECTOR_G Can be changed: C2(1, 5), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Applications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 6 1