EasyManua.ls Logo

Siemens G130 - p0355[0...n] Motor damping resistance q axis; Mot R_damp q; p0356[0...n] Motor stator leakage inductance; Mot L_stator leak.; p0357[0...n] Motor stator inductance d axis; Mot L_stator d

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
147
2 Parameters
2.2 List of parameters
Description: Sets the damping resistance of the separately excited synchronous motor quadrature to the rotor direction (q axis).
This parameter value is automatically calculated using the motor model (p0340 = 1, 2).
Description: This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor
identification routine (p1910).
Induction motor, separately excited synchronous motor: Sets the rotor leakage inductance of the motor.
Synchronous motor: Sets the stator quadrature axis inductance of the motor.
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: If the stator leakage inductance (p0356) for induction motors is changed outside the commissioning phase (p0010 >
0), the magnetizing inductance (p0360) is automatically adapted to the new EMF (r0337). You are then advised to
repeat the measurement for the saturation characteristic (p1960).
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is, therefore, ideal for a
low current.
Description: Sets the stator direct-axis inductance of the synchronous motor.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor
identification routine (p1910).
Note: The parameter is not used for separately excited synchronous motors (p0300 = 5).
For permanent-magnet synchronous motors (p0300 = 2), this is the non-saturated value and is ideal for a low current.
p0355[0...n] Motor damping resistance q axis / Mot R_damp q
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [ohm] 300.00000 [ohm] 0.00000 [ohm]
p0356[0...n] Motor stator leakage inductance / Mot L_stator leak.
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0357[0...n] Motor stator inductance d axis / Mot L_stator d
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00000 [mH] 1000.00000 [mH] 0.00000 [mH]