EasyManua.ls Logo

Siemens G130 - p1085[0...n] CI: Speed limit in positive direction of rotation; n_limit pos; p1086[0...n] CO: Speed limit in negative direction of rotation; n_limit neg; r1087 CO: Speed limit negative effective; n_limit neg eff; p1088[0...n] CI: Speed limit in negative direction of rotation; n_limit neg

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
321
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the speed limit of the positive direction.
Description: Sets the speed limit for the negative direction.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Display and connector output for the active negative speed limit.
Dependency: Refer to: p1082, p1086, p1088
Description: Sets the signal source for the speed/velocity limit of the negative direction.
Description: Sets skip speed 1.
Dependency: Refer to: p1092, p1093, p1094, p1101
Notice: Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Note: The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
p1085[0...n] CI: Speed limit in positive direction of rotation / n_limit pos
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 1083[0]
p1086[0...n] CO: Speed limit in negative direction of rotation / n_limit neg
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 0.000 [rpm] -40000.000 [rpm]
r1087 CO: Speed limit negative effective / n_limit neg eff
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3050, 3095
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1088[0...n] CI: Speed limit in negative direction of rotation / n_limit neg
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 1086[0]
p1091[0...n] Skip speed 1 / n_skip 1
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 0.000 [rpm]

Table of Contents