Siemens G130 - p2220[0...n] BI: Technology controller fixed value selection bit 0; Tec_ctrl sel bit 0; p2221[0...n] BI: Technology controller fixed value selection bit 1; Tec_ctrl sel bit 1; p2222[0...n] BI: Technology controller fixed value selection bit 2; Tec_ctrl sel bit 2; p2223[0...n] BI: Technology controller fixed value selection bit 3; Tec_ctrl sel bit 3

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
566 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the signal source to select a fixed value of the technology controller.
Dependency: Refer to: p2221, p2222, p2223
Description: Sets the signal source to select a fixed value of the technology controller.
Dependency: Refer to: p2220, p2222, p2223
Description: Sets the signal source to select a fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2223
Description: Sets the signal source to select a fixed value of the technology controller.
Dependency: Refer to: p2220, p2221, p2222
Description: Display and connector output for the selected and active fixed value of the technology controller.
Dependency: Refer to: r2229
p2220[0...n] BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7950, 7951
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2221[0...n] BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7950, 7951
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2222[0...n] BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7950, 7951
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2223[0...n] BI: Technology controller fixed value selection bit 3 / Tec_ctrl sel bit 3
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7950, 7951
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r2224 CO: Technology controller fixed value effective / Tec_ctr FixVal eff
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7950, 7951
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1