SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
569
2 Parameters
2.2 List of parameters
Description: Sets the maximum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2238
Description: Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2237
Description: Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency: Refer to: p2230
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency: Refer to: r2250
p2237[0...n] Technology controller motorized potentiometer maximum value / Tec_ctrl mop max
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2238[0...n] Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2240[0...n] Technology controller motorized potentiometer starting value / Tec_ctrl mop start
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
r2245 CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7954
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]