Siemens G130 - p5314[0...n] Moment of inertia precontrol linear negative; J_est lin neg; p5315[0...n] Moment of inertia precontrol constant negative; J_est const neg; p5316[0...n] Moment of inertia precontrol change time moment of inertia; J_prectrl t J; p5350[0...n] Mot_temp_mod 1;3 boost factor at standstill; Standst boost_fact

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
739
2 Parameters
2.2 List of parameters
Description: Setting of the linear coefficients for moment of inertia precontrol in the negative direction when the moment of inertia
estimator is active.
The estimated moment of inertia is obtained according to the following formula:
Moment of inertia (J) = linear coefficient (p5314) * load torque + constant coefficient (p5315)
Dependency: The function module "Moment of inertia estimator" (r0108.10) must be activated for the "Moment of inertia precontrol"
function.
Refer to: p5310, r5311, p5312, p5313, p5315
Description: Setting of the constant coefficients for moment of inertia precontrol in the negative direction when the moment of
inertia estimator is active.
The estimated moment of inertia is obtained according to the following formula:
Moment of inertia (J) = linear coefficient (p5314) * load torque + constant coefficient (p5315)
Dependency: The function module "Moment of inertia estimator" (r0108.10) must be activated for the "Moment of inertia precontrol"
function.
Refer to: p5310, r5311, p5312, p5313, p5314
Description: Sets the change time for the moment of inertia for the moment of inertia precontrol.
Lower values mean that faster changes are possible.
For a higher value, this estimated value is smoothed more significantly.
Dependency: Refer to: p1400, p1560, p1562
Description: Sets the boost factor for the copper losses at standstill for motor temperature models 1 and 3.
The entered factor is active for speed n = 0 [rpm].
This factor is linearly reduced down to 1 between speeds n = 0 ... 1 [rpm].
p5314[0...n] Moment of inertia precontrol linear negative / J_est lin neg
VECTOR_G
(J_estimator)
Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-340.28235E36 [s²] 340.28235E36 [s²] 0.000000 [s²]
p5315[0...n] Moment of inertia precontrol constant negative / J_est const neg
VECTOR_G
(J_estimator)
Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Motor Unit group: 25_1 Unit selection: p0100
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-340.28235E36 [kgm²] 340.28235E36 [kgm²] 0.000000 [kgm²]
p5316[0...n] Moment of inertia precontrol change time moment of inertia / J_prectrl t J
VECTOR_G
(J_estimator)
Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
10.00 [ms] 5000.00 [ms] 500.00 [ms]
p5350[0...n] Mot_temp_mod 1/3 boost factor at standstill / Standst boost_fact
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
1.0000 2.0000 2.0000