2 Parameters
2.2 List of parameters
SINAMICS G130/G150
34 List Manual (LH2), 07/2016, A5E03263479A
2.2 List of parameters
Product: SINAMICS G130/G150, Version: 4806000, Language: eng
Objects: CU_G130_PN, CU_G150_PN, CU_G130_DP, CU_G150_DP, VECTOR_G, B_INF, TM31, TM120, TM150, TB30, TM54F_MA, TM54F_SL, ENC,
HUB
Description: Operating display for the Control Unit (CU).
Value: 0: Operation
10: Ready
20: Wait for run-up
25: Wait for automatic FW update of DRIVE-CLiQ components
31: Commissioning software download active
33: Remove/acknowledge topology error
34: Exit commissioning mode
35: Carry out first commissioning
70: Initialization
80: Reset active
99: Internal software error
101: Specify topology
111: Insert drive object
112: Delete drive object
113: Change drive object number
114: Change component number
115: Run parameter download
117: Delete component
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Description: Operating display for the drive.
Value: 0: Operation - everything enabled
10: Operation - set "enable setpoint" = "1" (p1142, p1152)
11: Operation - set "enable speed controller" = "1" (p0856)
12: Operation - RFG frozen, set "RFG start" = "1" (p1141)
13: Operation - set "enable RFG" = "1" (p1140)
14: Oper. - MotID, excit. running and/or brake opens, SS2, STOP C
15: Operation - open brake (p1215)
16: Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
17: Operation - braking with OFF3 can only be interrupted with OFF2
18: Operation - brake on fault, remove fault, acknowledge
19: Operation - armature short-circ./DC brake act. (p1230, p1231)
21: Ready for operation - set "Enable operation" = "1" (p0852)
22: Ready for operation - de-magnetizing running (p0347)
23: Ready for operation - set "Infeed operation" = "1" (p0864)
31: Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
35: Switching-on inhibited - carry out first commissioning (p0010)
41: Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
42: Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
r0002 Control Unit operating display / CU op_display
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 117 -
r0002 Drive operating display / Drv op_display
VECTOR_G Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 250 -