Siemens G130 - p1759[0...n] Motor model changeover delay time open;closed-loop control; MotMod t op_cl; p1760[0...n] Motor model with encoder speed adaptation Kp; MotMod wE n_ada Kp; p1761[0...n] Motor model with encoder speed adaptation Tn; MotMod wE n_ada Tn; r1762[0...1] Motor model deviation component 1; MotMod dev comp 1

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
452 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the minimum time for a transition from open-loop controlled to closed-loop controlled operation after the lower
changeover speed p1755 * (1 - p1756 / 100 %) has been exceeded.
Dependency: Refer to: p1755, p1756
Note: With p1759 = 2000 ms, the delay time becomes ineffective and the model changeover is determined by the output
frequency only (changeover for p1755).
Description: Sets the proportional gain Kp of the controller for speed adaptation with encoder
Description: Sets the integral-action time Tn of the controller for speed adaptation with encoder
Description: Induction motor (ASM):
Displays the referred imaginary system deviation for the adaptation circuit of the motor model.
Permanent-magnet synchronous motor (PMSM):
Displays the system deviation for speed adaptation.
r1762[0]: Angular deviation [rad-el] of the estimated EMF.
r1762[1]: Angular deviation [rad-el] of the low-level signal response for pulse technique.
Index: [0] = Deviation model 1
[1] = Deviation model 2
p1759[0...n] Motor model changeover delay time open/closed-loop control / MotMod t op_cl
VECTOR_G (n/M) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: PMSM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 2000 [ms] 0 [ms]
p1760[0...n] Motor model with encoder speed adaptation Kp / MotMod wE n_ada Kp
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 100000.000 1000.000
p1761[0...n] Motor model with encoder speed adaptation Tn / MotMod wE n_ada Tn
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 4 [ms]
r1762[0...1] Motor model deviation component 1 / MotMod dev comp 1
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6721, 6730,
6731
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
- - -