SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
111
2 Parameters
2.2 List of parameters
350: SINAMICS SL
400: SINAMICS DCM
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Displays the properties supported by the power unit hardware.
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Displays the properties supported by the power unit hardware.
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
r0204[0...n] Power unit hardware properties / PU HW property
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Device type DC/AC device AC/AC device -
01 RFI filter available Yes No -
02 Active Line Module available Yes No -
03 Smart Line Module available Yes No -
04 Basic Line Module available with thyristor
bridge
Yes No -
05 Basic Line Module available with diode
bridge
Yes No -
06 Liquid cooling with cooling unit (chassis PU) Yes No -
07 F3E regenerative feedback into the line
supply
Yes No -
08 Internal Braking Module Yes No -
09 Different cooling type supported Yes No -
12 Safe Brake Control (SBC) supported No Yes -
13 Safety Integrated supported Yes No -
14 Internal LC output filter Yes No -
15 Line voltage 1-phase 3-phase -
r0204[0...n] Power unit hardware properties / PU HW property
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Device type DC/AC device AC/DC device -
01 RFI filter available Yes No -
02 Active Line Module available Yes No -
03 Smart Line Module available Yes No -
04 Basic Line Module available with thyristor
bridge
Yes No -
05 Basic Line Module available with diode
bridge
Yes No -
06 Liquid cooling with cooling unit (chassis PU) Yes No -
07 F3E regenerative feedback into the line
supply
Yes No -
08 Internal Braking Module Yes No -
09 Different cooling type supported Yes No -
12 Safe Brake Control (SBC) supported No Yes -
13 Safety Integrated supported Yes No -
14 Internal LC output filter Yes No -
15 Line voltage 1-phase 3-phase -