2 Parameters
2.2 List of parameters
Description: Sets the signal source for terminal DI/DO 15 (X132.13 / X131.5you).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Prerequisite: The DI/DO must be set as an output (p0728.15 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Displays the status of digital outputs.
Notice: Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: Inversion using p0748 has been taken into account.
DI/DO: Bidirectional Digital Input/Output
Description: Setting to invert the signals at the digital outputs.
p0745 BI: CU signal source for terminal DI/DO 15 / CU S_src DI/DO 15
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2119, 2133
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r0747 CU digital outputs status / CU DO status
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 2130, 2131,
2132, 2133
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X122.9/X121.7) High Low -
09 DI/DO 9 (X122.10/X121.8) High Low -
10 DI/DO 10 (X122.12/X121.10) High Low -
11 DI/DO 11 (X122.13/X121.11) High Low -
12 DI/DO 12 (X132.9/X131.1) High Low -
13 DI/DO 13 (X132.10/X131.2) High Low -
14 DI/DO 14 (X132.12/X131.4) High Low -
15 DI/DO 15 (X132.13/X131.5) High Low -
p0748 CU invert digital outputs / CU DO inv
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 2030, 2031,
2130, 2131, 2132, 2133
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
08 DI/DO 8 (X122.9/X121.7) Inverted Not inverted -
09 DI/DO 9 (X122.10/X121.8) Inverted Not inverted -
10 DI/DO 10 (X122.12/X121.10) Inverted Not inverted -
11 DI/DO 11 (X122.13/X121.11) Inverted Not inverted -
12 DI/DO 12 (X132.9/X131.1) Inverted Not inverted -
13 DI/DO 13 (X132.10/X131.2) Inverted Not inverted -
14 DI/DO 14 (X132.12/X131.4) Inverted Not inverted -
15 DI/DO 15 (X132.13/X131.5) Inverted Not inverted -