SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
271
2 Parameters
2.2 List of parameters
Implementation:
MDS0: p0827[0] = 4, interconnect output to switch contactor 0 to r0830.4, p0831[4] = "input, feedback signal,
contactor 0"
MDS1: p0827[1] = 5, interconnect output to switch contactor 1 to r0830.5, p0831[5] = "input, feedback signal,
contactor 1"
The following sequence applies when changing over from MDS0 to MDS1:
1. Status bit r0830.4 is deleted. When the feedback signal (p0831[4]) is connected, the system waits until the
feedback signal "contactor open" is displayed. If the feedback signal is not connected, then the system waits for the
switch-off interlocking time of 320 ms.
2. Status bit r0830.5 is set. If the feedback signal (p0831[5]) is connected, the system waits until the feedback signal
"contactor closed" is displayed. If the feedback signal is not connected, then the system waits for the switch-on
interlocking time of 160 ms.
Index: [0] = Feedback signal contactor 0
[1] = Feedback signal contactor 1
[2] = Feedback signal contactor 2
[3] = Feedback signal contactor 3
[4] = Feedback signal contactor 4
[5] = Feedback signal contactor 5
[6] = Feedback signal contactor 6
[7] = Feedback signal contactor 7
[8] = Feedback signal contactor 8
[9] = Feedback signal contactor 9
[10] = Feedback signal contactor 10
[11] = Feedback signal contactor 11
[12] = Feedback signal contactor 12
[13] = Feedback signal contactor 13
[14] = Feedback signal contactor 14
[15] = Feedback signal contactor 15
Description: Displays the status word of the contactor feedback signals when changing over a motor.
Dependency: Refer to: p0831
r0832.0...15 CO/BO: Mot. changeover contactor feedback sig. status word / Mot_chng fdbk ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Feedback signal contactor 0 Closed Opened -
01 Feedback signal contactor 1 Closed Opened -
02 Feedback signal contactor 2 Closed Opened -
03 Feedback signal contactor 3 Closed Opened -
04 Feedback signal contactor 4 Closed Opened -
05 Feedback signal contactor 5 Closed Opened -
06 Feedback signal contactor 6 Closed Opened -
07 Feedback signal contactor 7 Closed Opened -
08 Feedback signal contactor 8 Closed Opened -
09 Feedback signal contactor 9 Closed Opened -
10 Feedback signal contactor 10 Closed Opened -
11 Feedback signal contactor 11 Closed Opened -
12 Feedback signal contactor 12 Closed Opened -
13 Feedback signal contactor 13 Closed Opened -
14 Feedback signal contactor 14 Closed Opened -
15 Feedback signal contactor 15 Closed Opened -