2 Parameters
2.2 List of parameters
SINAMICS G130/G150
428 List Manual (LH2), 07/2016, A5E03263479A
Description: Threshold for setpoint/actual value tracking of the stator current in the q axis of the current model.
Description: Sets the minimum stator current for separately excited synchronous motors (SESM).
A negative value means that the field-generating stator current (d-axis) has a negative sign. The valid value is
internally limited to 50% of the rated motor current (p0305).
Description: Sets the speed where a change is made from the inner to the outer cos phi = 1.
If the value that is entered exceeds the rated speed, then a change is made to the inner cos phi = 1 over the complete
speed range.
Description: Sets the smoothing time constant for the setpoint of the field-generating current components.
The current filtered in this way is included in the calculation of the cos phi.
Description: Displays the steady-state field generating current setpoint (Id_set).
p1619[0...n] Setpoint/actual value tracking threshold / SetAct track thrsh
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: 6_2 Unit selection: p0505
Not for motor type: ASM, PMSM, REL Scaling: p2002 Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p1620[0...n] Stator current minimum / I_stator min
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: 6_2 Unit selection: p0505
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
-10000.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p1621[0...n] Changeover speed inner cos phi = 1 / n_chngov cos phi=1
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: 3_1 Unit selection: p0505
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 0.00 [rpm]
p1622[0...n] Field-generating current setpoint smoothing time constant / Id_setp T_smth
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.1 [ms] 200.0 [ms] 20.0 [ms]
r1623[0...1] Field-generating current setpoint (steady-state) / Id_set stationary
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6723, 6726,
6727
P-Group: Displays, signals Unit group: 6_2 Unit selection: p0505
Not for motor type: PMSM, REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]