Siemens G130 - p9554 SI Motion transition time STOP E to SOS (SBH) (Control Unit); SI Mtn t E­>SOS CU; p9555 SI Motion transition time STOP F to STOP B (Control Unit); SI Mtn t F­>B CU; p9556 SI Motion STOP A delay time (Control Unit); SI Mtn IL t_del CU; p9557 SI Motion STO test time (Control Unit); SI Mtn IL t_test

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
953
2 Parameters
2.2 List of parameters
Description: Sets the transition time from STOP E to "Safe Operating Stop" (SOS).
Dependency: Refer to: p9354
Note: The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SOS: Safe Operating Stop / SBH: Safe operating stop
Description: Sets the transition time from STOP F to STOP B.
Dependency: Refer to: C01711
Note: The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Description: Sets the delay time for STOP A after STOP B.
In the case of encoderless motion monitoring functions with safe brake ramp monitoring (p9506 = 1) and the OFF3
ramp enabled at the same time (p9507.3 = 0), the parameter has no effect.
Dependency: Refer to: p9560
Refer to: C01701
Note: The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Description: Sets the time after which STO must be active when initiating the test stop.
Dependency: Refer to: C01798
Note: A change only becomes effective after a POWER ON.
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
p9554 SI Motion transition time STOP E to SOS (SBH) (Control Unit) / SI Mtn t E->SOS CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 600000.00 [ms] 100.00 [ms]
p9555 SI Motion transition time STOP F to STOP B (Control Unit) / SI Mtn t F->B CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2819
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 600000.00 [ms] 0.00 [ms]
p9556 SI Motion STOP A delay time (Control Unit) / SI Mtn IL t_del CU
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 2819
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 3600000.00 [ms] 100.00 [ms]
p9557 SI Motion STO test time (Control Unit) / SI Mtn IL t_test
VECTOR_G Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 10000.00 [ms] 100.00 [ms]