Siemens G130 - r1444 Speed controller speed setpoint steady-state (static); n_ctrl n_set stat; r1445 CO: Actual speed smoothed; n_act smooth; p1451[0...n] Motor model speed actual value smoothing time sensorless; Mot_mod n_act t_sm; p1452[0...n] Speed controller speed actual value smoothing time (sensorless); n_C n_act T_s SL

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
393
2 Parameters
2.2 List of parameters
Description: Displays the sum of all speed setpoints that are present.
The following sources are available for the displayed setpoint:
- setpoint at the ramp-function generator input (r1119).
- speed setpoint 1 (p1155).
- speed setpoint 2 (p1160).
- speed setpoint for the speed pre-control (p1430).
- setpoint from DSC (for DSC active).
- setpoint via PC (for master control active).
Dependency: Refer to: r1119, p1155, p1160
Description: Display and connector output for the actual smoothed speed actual value of the speed control.
Description: Sets the smoothing time for the speed actual value calculated by the motor model in sensorless operation.
Description: Sets the smoothing time for the actual speed of the speed controller for encoderless closed-loop speed control.
Note: The smoothing must be increased if there is gear backlash. For longer smoothing times, the integral time of the
speed controller must also be increased (e.g. using p0340 = 4).
r1444 Speed controller speed setpoint steady-state (static) / n_ctrl n_set stat
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 5030
P-Group: Closed-loop control Unit group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r1445 CO: Actual speed smoothed / n_act smooth
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6040
P-Group: Closed-loop control Unit group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1451[0...n] Motor model speed actual value smoothing time sensorless / Mot_mod n_act t_sm
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 4 [ms]
p1452[0...n] Speed controller speed actual value smoothing time (sensorless) / n_C n_act T_s SL
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6020, 6040
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 32000.00 [ms] 10.00 [ms]