2 Parameters
2.2 List of parameters
Description: Displays the actual resistance value of the temperature sensor connected at the Terminal Module.
Note: The maximum measurable resistance value is approx. 1720 Ohm.
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
Description: Sets the fault threshold/alarm threshold for Terminal Module 120 (TM120).
A35211 is initiated, if the temperature actual value r4105[0] > p4102[0]
F35207 is initiated if the temperature actual value r4105[0] > p4102[1] or timer p4103[0] has expired
A35212 is initiated, if the temperature actual value r4105[1] > p4102[2]
F35208 is initiated if the temperature actual value r4105[1] > p4102[3] or timer p4103[1] has expired
A35213 is initiated, if the temperature actual value r4105[2] > p4102[4]
F35209 is initiated if the temperature actual value r4105[2] > p4102[5] or timer p4103[2] has expired
A35214 is initiated, if the temperature actual value r4105[3] > p4102[6]
F35210 is initiated if the temperature actual value r4105[3] > p4102[7] or timer p4103[3] has expired
For alarms A35211, A35212, A35213, A35214 the following applies:
- Remains until the temperature actual value (r4105[0...3]) reaches or falls below the value (p4102[0, 2, 4, 6] -
hysteresis).
For fault F35207, F35208, F35209, F35210 the following applies:
- Remains until the temperature actual value (r4105[0...3]) reaches or falls below the value (p4102[1, 3, 5, 7] -
hysteresis) and the fault has been acknowledged.
- the hysteresis value is 5 K and cannot be changed.
Index: [0] = Channel 0 alarm threshold (A35211)
[1] = Channel 0 fault threshold (F35207)
[2] = Channel 1 alarm threshold (A35212)
[3] = Channel 1 fault threshold (F35208)
[4] = Channel 2 alarm threshold (A35213)
[5] = Channel 2 fault threshold (F35209)
[6] = Channel 3 alarm threshold (A35214)
[7] = Channel 3 fault threshold (F35210)
Dependency: Refer to: p4103
Notice: Fault F35207 ... F35210 only causes the drive to shut down if there is at least one BICO interconnection between the
drive and TM120.
For p4102[0...7] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100[0...3] = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...7] must be set <= 250 °C.
Note: The temperature sensor is connected to the following terminals:
X521.2(+) and X521.1(-) = channel 0
X521.4(+) and X521.3(-) = channel 1
X521.6(+) and X521.5(-) = channel 2
X521.8(+) and X521.7(-) = channel 3
r4101 TM31 sensor resistance / TM31 R_sensor
TM31 Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 9576
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p4102[0...7] TM120 fault threshold/alarm threshold / TM120 F/A_thresh
TM120 Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9605, 9606
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-48 [°C] 251 [°C] 251 [°C]