SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
429
2 Parameters
2.2 List of parameters
Description: Displays the limited field-generating current setpoint (Id_set).
This value comprises the steady-state field-generating current setpoint r1623 and a dynamic component that is only
set when changes are made to the flux setpoint.
Description: Sets the gain factor to weight the excitation current setpoint.
Description: Displays the calculated excitation current setpoint.
The following applies for index 0:
For direct excitation, the value is referred to p0390. For brushless excitation, the value is referred to p0690.
The following applies for index 1:
The value is referred to p0390.
Index: [0] = Excitation current of the excitation equipment
[1] = Excitation current for direct excitation
Dependency: Refer to: p0390, p0690
Description: Displays the load angle of the current model.
r1624 Field-generating current setpoint total / Id_setp total
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6640, 6721,
6723, 6727
P-Group: Displays, signals Unit group: 6_2 Unit selection: p0505
Not for motor type: REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1625[0...n] Excitation current setpoint calibration / I_exc_setp cal
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
10.0 [%] 200.0 [%] 100.0 [%]
r1626[0...1] CO: Excitation current setpoint / I_exc_setp
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1627 CO: Current model load angle / I_mod load angle
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: p2005 Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]