2 Parameters
2.2 List of parameters
SINAMICS G130/G150
434 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the switch-off delay time to shut down the excitation equipment.
Note: The delay time starts if, when switching off, r0863.0 = 0.
r1648.0 and r1648.3 are reset at the end of the delay time.
Description: Displays the control word for the excitation equipment.
Note: For bit 00:
This bit is set dependent on r0863.0.
Description: Displays the status word of the excitation equipment.
Dependency: Refer to: p1645
p1647 Excitation switch-off delay time / Exc t_off
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6495
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 5.0 [s] 0.8 [s]
r1648.0...11 CO/BO: Excitation control word / Excitation STW
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 6495
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power up excitation Yes No -
01 Excitation no OFF2 Yes No -
02 Excitation no OFF3 Yes No -
03 Excitation operation enable Yes No -
07 Excitation acknowledge fault Yes No -
10 Reserved - - -
11 Reserved - - -
r1649.0...8 CO/BO: Excitation status word / Excitation ZSW
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 6495
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Excitation ready for switching on feedback
signal
Yes No -
01 Excitation ready feedback signal Yes No -
02 Excitation operational feedback signal Yes No -
03 Excitation group signal fault Yes No -
07 Excitation group signal alarm Yes No -
08 Excitation at the voltage limit Yes No -