SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1645
4 Faults and alarms
4.2 List of faults and alarms
A09000 Webserver security: password for "Administrator" user not set
Message value: -
Message class: General drive fault (19)
Drive object: All objects
Component: Control Unit (CU) Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: Webserver security: password for "Administrator" user not set
Remedy: Enter the password for user "Administrator"
A13000 License not adequate
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Component: Control Unit (CU) Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: - for the drive unit, the options that require a license are being used but the licenses are not sufficient.
- an error occurred when checking the existing licenses.
Alarm value (r2124, interpret decimal):
0:
The existing license is not sufficient.
1:
An adequate license was not able to be determined as the memory card with the required licensing data was
withdrawn in operation.
2:
An adequate license was not able to be determined as there is no licensing data available on the memory card.
3:
An adequate license was not able to be determined as there is a checksum error in the license key.
4:
An internal error occurred when checking the license.
Remedy: For alarm value = 0:
Additional licenses are required and these must be activated (p9920, p9921).
For alarm value = 1:
With the system powered down, re-insert the memory card that matches the system.
For alarm value = 2:
Enter and activate the license key (p9920, p9921).
For alarm value = 3:
Compare the license key (p9920) entered with the license key on the certificate of license.
Re-enter the license key and activate (p9920, p9921).
For alarm value = 4:
- carry out a POWER ON.
- upgrade firmware to later version.
- contact Technical Support.
A13001 Error in license checksum
Message value: -
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Component: Control Unit (CU) Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: When checking the checksum of the license key, an error was detected.
Remedy: Compare the license key (p9920) entered with the license key on the certificate of license.
Re-enter the license key and activate (p9920, p9921).