2 Parameters
2.2 List of parameters
SINAMICS G130/G150
614 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the actual value of the voltage measured at the 10 V input 2 of the Voltage Sensing Module (VSM).
Dependency: Refer to: p3670
Note: 10 V input 2: Terminals X520.3 and X520.4
Description: Sets the signal source to inhibit the internal Braking Module.
BI: p3680 = 1 signal:
The Braking Module is inhibited.
BI: p3680 = 0 signal:
The Braking Module is enabled.
Dependency: Refer to: A06904
Caution: When the Braking Module is inhibited, no energy can be dissipated in the braking resistor.
Description: Sets the signal source to activate the DC link fast discharge for an internal braking module.
When the following conditions apply, the DC link fast discharge is started later with delay time (p3682):
- BI: p3681 = 1 signal.
- an external line contactor is opened via r0863.1 "energize contactor".
The DC link fast discharge is interrupted when the following conditions apply:
- BI: p3681 = 0 signal.
- ON command for the infeed.
Recommendation: The DC link fast discharge should be activated if there is an external line contactor and is correctly interconnected
(r0863.1, p0860). If the DC link fast discharge is not activated together with an external line contactor, then faults can
occur when precharging (e.g. F30027).
Dependency: Refer to: p3682
Refer to: F30027
Notice: The parameter is only effective for Basic Line Modules with the internal Braking Module (this is valid for Basic Line
Modules with a power rating of less than 100 kW).
r3674[0...n] CO: VSM 10 V input 2 actual value / VSM inp 2 U_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
p3680 BI: Braking Module internal inhibit / BM int inhib
B_INF Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p3681 BI: Activating Braking Module internal DC link fast discharge / BM intDCdischg act
B_INF Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0