SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1379
4 Faults and alarms
4.2 List of faults and alarms
F01039 (A) ACX: Writing to the parameter back-up file was unsuccessful
Message value: %1
Message class: Hardware/software error (1)
Drive object: All objects
Component: Control Unit (CU) Propagation: LOCAL
Reaction: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF2)
Acknowledge: IMMEDIATELY
Cause: Writing to at least one parameter back-up file PSxxxyyy.*** in the non-volatile memory was unsuccessful.
- in the directory /USER/SINAMICS/DATA/ at least one parameter back-up file PSxxxyyy.*** has the "read only" file
attribute and cannot be overwritten.
- there is not sufficient free memory space available.
- the non-volatile memory is defective and cannot be written to.
Fault value (r0949, interpret hexadecimal):
dcba hex
a = yyy in the file names PSxxxyyy.***
a = 000 --> consistency back-up file
a = 001 ... 062 --> drive object number
a = 070 --> FEPROM.BIN
a = 080 --> DEL4BOOT.TXT
a = 099 --> PROFIBUS parameter back-up file
b = xxx in the file names PSxxxyyy.***
b = 000 --> data save started with p0977 = 1 or p0971 = 1
b = 010 --> data save started with p0977 = 10
b = 011 --> data save started with p0977 = 11
b = 012 --> data save started with p0977 = 12
d, c:
Only for internal Siemens troubleshooting.
Remedy: - check the file attribute of the files (PSxxxyyy.***, CAxxxyyy.***, CCxxxyyy.***) and, if required, change from "read
only" to "writeable".
- check the free memory space in the non-volatile memory. Approx. 80 kbyte of free memory space is required for
every drive object in the system.
- replace the memory card or Control Unit.
Reaction upon A: NONE
Acknowl. upon A: NONE
F01040 Save parameter settings and carry out a POWER ON
Message value: -
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: B_INF, CU_G130_DP, CU_G130_PN, CU_G150_DP, CU_G150_PN, ENC, HUB, TB30, TM120, TM150, TM31,
TM54F_MA, TM54F_SL
Component: None Propagation: GLOBAL
Reaction: OFF2
Acknowledge: POWER ON
Cause: A parameter was changed in the drive system which means that it is necessary to save the parameters and re-boot.
Remedy: - save parameters (p0971, p0977).
- carry out a POWER ON (switch-off/switch-on) for all components.
Then:
- upload the drive unit (commissioning software).