2 Parameters
2.2 List of parameters
SINAMICS G130/G150
252 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the rated current of the excitation equipment for the excitation machine for brushless excitation.
Dependency: Refer to: r1626
Notice: For a value = 0, brushless excitation is not activated.
Note: BLE: brushless excitation
Description: Sets the saturated inductance of the excitation machine for brushless excitation.
A negative value can also be entered as part of optimizing coefficients.
Notice: For a value = 0, brushless excitation is not activated.
Note: BLE: brushless excitation
Description: Sets the ratio between the stator and rotor of the excitation machine for brushless excitation.
The ratio of the rated excitation current of the main machine to the associated excitation current of the excitation
machine at the rated point of the machine is entered.
Dependency: Refer to: p0311, p0390
Notice: For a value = 0, brushless excitation is not activated.
Note: BLE: brushless excitation
Description: Sets the pole pair number of the exciter machine for brushless excitation.
Notice: For a value = 0, brushless excitation is not activated.
Note: BLE: brushless excitation
p0690[0...n] Brushless excitation rated current / BLE I_rated
VECTOR_G (n/M) Can be changed: C2(3), T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.00 [A] 100.00 [A] 0.00 [A]
p0693[0...n] Brushless excitation inductance d-axis saturated / BLE L_d sat
VECTOR_G (n/M) Can be changed: C2(3), U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
-1000.00000 [mH] 1000.00000 [mH] 0.00000 [mH]
p0696[0...n] Brushless excitation ratio / BLE ratio
VECTOR_G (n/M) Can be changed: C2(3), U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0.000 1000.000 0.000
p0697[0...n] Brushless excitation number of pole pairs / BLE PolePairNo
VECTOR_G (n/M) Can be changed: C2(3), T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: MDS, p0130 Func. diagram: 6727
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
0 20 0