SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
699
2 Parameters
2.2 List of parameters
Note: SMI: SINAMICS Sensor Module Integrated
DQI: DRIVE-CLiQ Sensor Integrated
Help for error value = 11:
- Save the data for the original SMI on the memory card.
- Use an SMI with a suitable hardware version.
Help for error value = 12:
- set the correct component number or connect the component.
Help for error value = 13:
- Use a memory card with more memory space.
Help for error value = 14:
- Create a data backup on the memory card corresponding to the SMI type.
Help for error value = 15:
- check the DRIVE-CLiQ wiring for the component.
Help for error value = 16:
- check the DRIVE-CLiQ wiring for the component.
Help for error value = 17:
- Save the data for the original SMI on the memory card.
Help for error value = 18:
- set parameter p4693 to an appropriate value.
Help for error value = 19:
- Perform an SMI delete or use a blank SMI.
Help for error value = 20:
- Use an SMI that is not blank.
Help for error value = 21:
- set the correct component number (p4690).
Note for error value = 22:
- Data cannot be downloaded for component.
Help for error value = 35:
- Reset parameter p4691 to 30.
Help for error value = 37:
- set the access level to Expert or higher.
Help for error value = 38:
- insert the SMI/DQI into the actual topology as an additional component (component number >= 200).
- set the component number from the actual topology (p4690 >= 200).
- set the correct component number (p4690 >= 200).
Note for error value = 39:
- SMI already deleted or too old. Delete not possible.
Description: Setting to back up the data of all SMIs and DQIs featured in the target topology.
Value: 0: Inactive
1: Save data of all SMIs and DQIs
10: Save all data successful
13: Insufficient memory space for backup
16: Transfer fault during data backup
20: Component does not contain any data
29: Not all components from target topology saved
p4692 SMI spare part save data of all SMIs / Save SMI data
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 29 0