Siemens G130 - r4112[0...2] CO: TM150 group temperature actual value maximum value; TM150 grp temp max; r4113[0...2] CO: TM150 group temperature actual value minimum value; TM150 grp temp min

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
678 List Manual (LH2), 07/2016, A5E03263479A
Dependency: Refer to: r4105, r4112, r4113, r4114
Notice: When forming groups, it must be ensured that in one particular group, only temperature channels with the following
sensor types are included:
- "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6), real temperature actual value
or alternatively
- "PTC thermistor", "bimetallic NC contact" (p4100[0...11] = 1, 4), fictitious temperature actual value (-50 °C, 250 °C)
If these sensor types are combined within one group, then the calculated values for maximum, minimum and average
value will be falsified.
Note: Active and inactive temperature channels can be included in one group. However, when calculating the values
(r4112, r4113, r4114) only the active temperature channels with valid actual value are taken into account
(r4105[0...11] not equal to -300 °C).
Description: Display and connector output for the maximum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation: The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4113, r4114
Description: Display and connector output for the minimum value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation: The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4112, r4114
07 Temperature channel 7 Yes No -
08 Temperature channel 8 Yes No -
09 Temperature channel 9 Yes No -
10 Temperature channel 10 Yes No -
11 Temperature channel 11 Yes No -
r4112[0...2] CO: TM150 group temperature actual value maximum value / TM150 grp temp max
TM150 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9625
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r4113[0...2] CO: TM150 group temperature actual value minimum value / TM150 grp temp min
TM150 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9625
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]