2 Parameters
2.2 List of parameters
SINAMICS G130/G150
776 List Manual (LH2), 07/2016, A5E03263479A
Description: Setting to backup/import/delete NVRAM data.
NVRAM data are non-volatile data in the device (e.g. fault buffer).
For NVRAM data actions, the following data are excluded:
- crash diagnostics
- CU operating hours counter
- CU temperature
- safety logbook
Value: 0: Inactive
1: NVRAM data backup to memory card
2: Import NVRAM data from the memory card
3: Delete NVRAM data in the device
10: Error when clearing
11: Error when backing up, memory card not available
12: Error when backing up, insufficient memory space
13: Error when backing up
14: Error when importing, memory card not available
15: Error when importing, checksum error
16: Error when importing, no NVRAM data available
17: Error when importing
Notice: For value = 2, 3:
These actions are only possible when pulses are inhibited.
Note: After the action has been successfully completed, the parameter is automatically set to zero.
The actions importing and deleting NVRAM data immediately initiate a warm restart.
If the procedure was not successfully completed, then an appropriate fault value is displayed (p7775 >= 10).
Description: Service parameter to internally document repairs.
After a component has been replaced, this must be confirmed using p7786.x = 0/1.
When acknowledging a replacement, the "Generate report" function is automatically executed.
p7786.x is automatically set to 0 after POWER ON.
Notice: This write process can take several minutes.
Note: The power unit involved can be assigned the correct P index using p0124 (power unit detection via LED).
p7775 NVRAM data backup/import/delete / NVRAM backup
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: C1, U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: All groups Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 17 0
p7786[0...n] Service report / Service report
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Control Interface Module (CIM) replaced Yes No -
01 Valve 1 replaced Yes No -
02 Valve 2 replaced Yes No -
03 Valve 3 replaced Yes No -
04 Valve 4 replaced Yes No -
05 Valve 5 replaced Yes No -
06 Valve 6 replaced Yes No -
15 Generate report Yes No -