2 Parameters
2.2 List of parameters
SINAMICS G130/G150
154 List Manual (LH2), 07/2016, A5E03263479A
Notice: For permanent magnet synchronous motors (PMSM), the following applies:
If the parameters are not set as specified, i.e. not in ascending order and to more than 20 %, the unsaturated
quadrature inductance (p0356) is always used for quadrature axis flux calculation purposes.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Displays the motor stator resistance at an ambient temperature (p0625).
The value does not include the cable resistance.
Dependency: Refer to: p0625
Description: Displays the total cable resistance between Motor Module and motor, as well as the internal converter resistance.
Dependency: Refer to: r0238, p0352
Description: Displays the rated motor stator resistance at rated temperature (total of p0625 and p0627).
Dependency: Refer to: p0627
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Displays the rotor/secondary section resistance of the motor for the ambient temperature p0625.
For separately excited synchronous motors:
Displays the damping resistance in the rotor direction (d-axis).
Dependency: Refer to: p0625
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
r0370[0...n] Motor stator resistance cold / Mot R_stator cold
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0372[0...n] Total power unit cable resistance / PU cable R tot
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0373[0...n] Motor rated stator resistance / Mot R_stator rated
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: PMSM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0374[0...n] Motor rotor resistance cold / damping resistance d axis / Mot R_r cold/R_D d
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: PMSM, REL, RESM Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]